Split dehumidifier · 350 pints/day

VKIN UCDA-D360DCT Ducted split dehumidifier that keeps compressor heat out of the room

A ducted split dehumidifier with three-pipe heat recovery. Because the indoor and outdoor units are separated, 100% of the compressor heat stays outside the room — the reason a split beats a portable once the latent load gets serious. Runs a constant-temperature mode that pulls 360 pints/day while holding temperature, and complies with California Title 24.

350 pints/dayat 80°F / 60% RH
360 pints/dayconstant-temperature mode
8.6 pints/kWhenergy factor 4.1 L/kWh
800 CFM0–0.8 in W.C. ducted
Title 24California compliant

Where it fits

Built for these rooms.

Flower rooms where the AC can’t keep up

Adds dedicated moisture removal when plant transpiration outruns what your cooling system pulls.

Adding to existing HVAC

Runs from its wired controller or a standard 24V thermostat, alongside the cooling you already have.

Heat-sensitive rooms

Because the compressor sits outdoors, removing water doesn’t dump heat into the room the way a portable or stand-alone dehumidifier does.

Split design

Water out. Heat outside.

  1. Pull water out indoors

    The ducted indoor cabinet draws room air across its coil and condenses the moisture out.

  2. Keep the heat outside

    The compressor and condenser sit in the outdoor unit, so their heat is rejected outdoors, not into your flower room.

  3. Hold the room

    Three-pipe heat recovery and a constant-temperature mode remove water without swinging room temperature.

Manufacturer data

UCDA-D360DCT specifications

VKIN UCDA-D360DCT
VKIN UCDA-D360DCT
Water removal350 pints/day · 14.6 pint/h (DB 80°F, RH 60%)
Constant-temp mode360 pints/day · 15 pint/h (DB 80°F, RH 60%)
Water removal @ 75°F224 pints/day (RH 50%) · 12,800 Btu/h
Water removal @ 65°F105 pints/day (RH 50%) · 8,000 Btu/h
Cooling capacity20,000 Btu/h
Power input1,700 W · 7.54 A
Efficiency8.6 pints/kWh · EF 4.1 L/kWh
Constant-temp efficiency8.7 pints/kWh · EF 4.1 L/kWh
Indoor airflow800 / 650 / 500 CFM
External static pressureRated 0 · range 0–0.8 in W.C.
Indoor unit33″ × 27″ × 18″ · 46/37/28 dB(A)
Outdoor unit33.2″ × 27.8″ × 13.3″ · 51 dB(A)
Drain connection1/2″ OD
Refrigerant piping1/4 – 3/8 – 1/2″ · max 100 ft · 33 ft level difference
Refrigerant / throttleR454B · EEV
Max. allowable pressure609 psi
FiltrationMERV-13
ControlWired controller / 24V thermostat
Operating rangeIndoor 41–88°F · Outdoor 5–118°F
ComplianceCalifornia Title 24
Power supply208–277V · 1Ph · 60Hz

Specifications are from the manufacturer datasheet and may change without notice. The unit rating plate governs.

Questions

UCDA-D360DCT FAQ

How much water does the UCDA-D360DCT remove?

350 pints per day (14.6 pints/hour) at 80°F and 60% RH, 224 pints per day at 75°F and 50% RH, and 105 pints per day at 65°F and 50% RH. Constant-temperature mode removes 360 pints per day at 80°F and 60% RH.

Why a split dehumidifier instead of a portable?

A portable unit rejects its compressor heat into the room, which the AC then has to remove. The D360DCT’s compressor is in the outdoor unit, so that heat stays outside.

What power and line set does it need?

Single-phase 208–277V, 60 Hz, drawing 1,700 W at 7.54 A. Refrigerant lines are 1/4″, 3/8″ and 1/2″, up to 100 ft long with 33 ft of vertical difference.

How is it controlled?

With the included wired controller, or with a 24V thermostat or humidistat signal.

The VKIN lineup